  • Pre-engineered fixed aerosol fire protection system wall mounted

    Wall-mounted aerosol fire protection system is also called a "suspension system", it is a kind of aerosol for total flooding the fire hazards, but installed on the wall by an installation bracket, compared with other styles, the best advantage of suspension aerosol is that could be installed on the wall and space-saving.

    enquiry
    • Specifications
    • Aerosol Features and Characteristics
    • Aerosol Application

    Below are the specifications and dimensions of wall-mounted type aerosol generators and fire protection system devices:

    • Installation style: Wall mounted, to install on the wall or the ceiling above, better no more than 5 meters in height.
    • Aerosol cylinder shape: round cylinder shape, just like an indoor air conditioner.
    • Aerosol cylinder color: Red and other OEM colors.
    • Aerosol agent weight: 3 kilograms, 5 kilograms, 7.5 kilograms, 8 kilograms, and 10 kilograms for different models and different designs.
    • Aerosol agent storage pressure: normal.
    • Aerosol device model number: AW-QRR3GW/S, AW-QRR5GW/S, AW-QRR7.5GW/S, AW-QRR8GW/S, AW-QRR10GW/S, for details please refer to our “Installation Manual”.
    • Aerosol design concentration: 130 grams to 150 grams per cubic meter, for details please inquire to discuss.
    • Dimension size of the product: normally diameter is 300 millimeters and the length is 700 millimeters, could be designed as per specialty.
    • Start-up mode: Electrical or electronics by power supply of DC 3 to 24 Volt, and TAG thermal activation generator could be used together with this device.
    • Working and operation temperature: from -40°C to +70°C.
    • Extinguishing time: If the aerosol mass is less than 1 kilogram, then the extinguishing time is less than 40 seconds, and if the aerosol mass weight is more than 1 kilogram, then the extinguishing time is less than 120 seconds.
    • Downtime: less than 30 seconds.
    • Outside shell temperature during the period of discharging: less than 180°C at 5 millimeters distance from the outlet location.
    • Shell temperature at the device: less than 100 degrees Celsius.
    • Resistance of direct current: one to eight ohms.
    • Activation current and time: 1 Ann every 5 milliseconds.
    • Minimum activation current and time: 250 Millie-amps each 5 milliseconds.
    • Maximum safety current and time: 150 milliamps each 5 minutes.
    • The life cycle of condensed solid aerosol compound: 7 to 10 years.
    • Wire connection terminal: 5 cores, including 2 cores for activation purposes, 2 cores for test report purposes, and one for anti-static.
    • Connection mode between devices: series connection, Series circuit.

    For now for “Main material description”, “Relative standard”, “External and Internal Structure”, “Attention for transport and storage”, and “After-sales service” please refer to Floor Type Aerosol, or as per our “INSTALLATION MANUAL“.

    Wall-mounted aerosol model number:

    • AW-QRR5GW/S with aerosol mass quality of 5 kilograms, protect of volume at 35 cubic meters each device.
    • AW-QRR7.5GW/S with aerosol mass quality of 7.5 kilograms, protect of volume at 53 cubic meters for each device.
    • AW-QRR8GW/S with aerosol mass quality of 8.0 kilograms, protect of volume at 57 cubic meters for each device.

    Attention for operation:

    • Please read the “Installation Manual” carefully before doing the installation job.
    • The installation and commissioning job must be done by a professional skilled personnel.
    • After installation, the fire extinguishing system and its device shall not move with ease.
    • When there is a fire, people must evacuate from the fire protection zone immediately, and before escaping, people should close the doors and windows quickly.
    • The life span of this kind of aerosol device is about 7 to 10 years.
    • After the aerosol device is discharged, people should wear a pair of gloves to remove it clean the device up, and do not touch the cylinder in case of gets burned.
    • It is forbidden to take apart the device, in case of any accident.
    • The fire alarm system’s standby power is forbidden to discharge in continuing 24 hours and the standby power should change every 4 years.
    • The inspector should disconnect the fire alarm control systems to inspect the system yearly and keep it recorded.
    • Before installation, the installer should make sure the device is powered off.

    Attention for installation:

    • Because this wall-mounted fixed aerosol fire protection system device is needed to install on the wall or the top of the ceiling, and each device will be several tens of kilograms in gross weight, so when installing it take care and make sure to firmly fix the bracket and screws.
    • Better to Install it at least 1/2 high of the room height.
    • Make sure the left side discharging outlet and right side discharging outlet are without any obstacles.

    Why we recommend of wall mounted aerosol for the market:
    Wall-mounted aerosol is mostly installed in computer rooms, data processing rooms, telecommunication rooms, and other buildings, and in China, we have many cases of installing it in the underground Integrated Pipe Gallery, which is a national project in China.
    Also, it covers more space and space-saving to install, some protection zones will need to require a device which is a space-saving device.
    An aerosol extinguishing device has with very high extinguishing ability.

    Safety Warning!
    Users should set warning signs in the following obvious locations, the words on the warning sign suggest like following:

    • inside the protection zone: “WARNINGS! This is S type aerosol fire extinguishing device protection zone, if you hear there is a fire alarm at the site, please escape immediately”.
    • At the location of the manual call point: “WARNING, When pressing down the manual call point button, please make sure there are no people at the site”.
    • Outside the protection zone: ” This protection zone is protected by aerosol fire extinguishing systems”.

    Device Maintenance
    to ensure the reliability of the hot aerosol fire extinguishing device, we should establish complete regulations for equipment inspection and maintenance, and make operation norms; the qualified inspector should inspect it and make a record regularly.
    During the maintenance period, the inspector must do an inspection job following relevant standards and specifications.
    1. Daily Maintenance (When the device is being in use)
    a. make sure the protection zone and fire alarm system control rooms are clean, dry, and well-ventilated.
    b. make sure the surface of the aerosol device and fire alarm control panel is without dust.
    c. check the nameplate of the aerosol device, that warning signs are intact, and that the check outlet of the aerosol device is not blocked.
    d. check whether the fire alarm system is at fault or not, or check whether it has an activation problem or not; if find any of the above problems, then please check and resolve it in time.
    2. Yearly Maintenance

    • Protection area opening situations, the aim of the protection area, protection types, quantities, and distribution of combustibles, factors should comply with fire protection standards and specifications.
    • Examine all aspects of the aerosol extinguishing devices, for example, to inspect whether all the components and parts are firmly fixed or not, and please clean up the device to make sure it will not have much dust.
    • After the aerosol units are put in use, their expiration date is about 7 to 10 years, after the expiration date, please try to contact the supplier for replacement.

    Aerosol fire protection systems have common features, normally described as follows:

    • The third aerosol technology, and refill with strontium nitrate and potassium nitrate of aerosol chemical powder, strontium nitrate takes a proportion of about 50%, and potassium nitrate takes about 10% to 20% proportion, china aerosol based compound is with advance technology and innovative.
    • it is non-toxic, non-corrosive, non-conductive, not have any residue after suppression.
    • It is Eco-friendly with zero value in Ozone-layer Depletion, Zero value in Global Warming Potential, and Low value in Atmospheric Life Time.
    • Space-saving and compact, simple construction, easy to install, easy to do system design, debugging, and installation.
    • Low in system maintenance after sale, not require years of inspection.

    Also, wall mounted type of aerosol devices have special characteristics, which are listed as follows:

    • Round cylinder shape like an indoor air conditioner.
    • Could be installed on the top ceiling of the room or the wall above the protection objective, it is space-saving for the project.
    • IP 67 in waterproof and dustproof performance.

    Remark: hereby IP is IP code, which means what is the grade of dust protection and water protection?

    Wall-mounted style of aerosol suppression system is also widely applied in many industries and protected objects across the post and telecommunication industry, mining industry, power industry, banking industry, and so on, including:

    • Computer room.
    • Server room.
    • Data processing room.
    • Power Generator room.
    • Power distribution room.
    • Cable tray.
    • Underground pipe gallery.
    • Substation.
    • UPS room.
    • EPS room.
    • Battery room.
    • Storage room.
    • Expensive medical room.
    • Museum.
    • Library.
    • Archives.
    • Vehicles engine room compartment.
    • Wind Power.
    • Health care room.
    • Some other machinery facilities and equipment.

    Aerosol fire extinguishing device and its system are applied in the following class Rating:

    • Class A fires: common fuels, such as wood or trash.
    • Class B fires: Flammable or combustible liquids, such as solvents and gasoline.
    • Class C fires Burning gases, such as natural gas.
    • Class E fires: Fires involving potentially energized electrical equipment.
    • Class F fire: Vegetable or animal cooking oils and fats, such as kitchens.

    An aerosol system is not suitable for the following sites:

    • Chemicals that can oxidize quickly without air, like Nitrocellulose, and gunpowder; or Chemicals that can break down by themselves, like hydrazine and some metal peroxides.
    • Oxidized metal, like potassium and sodium, etc; metal oxide, like potassium hydride, sodium hydride, etc; and Spontaneous combustion, like Phosphorus.
    • Deep fire of flammable solid.
    CATEGORY AND TAGS:
    PRODUCT, Wall mounted aerosol fire protection system