Below are specification and dimension of wall mounted type aerosol generators fire protection system device:
- Installation style: Wall mounted, to install on the wall or on the ceiling above, better no more than 5 meters in height.
- Aerosol cylinder shape: round cylinder shape, just like a indoor air conditioner.
- Aerosol cylinder color: Red and other OEM color.
- Aerosol agent weight: 3 kilograms, 5 kilograms, 7.5 kilograms, 8 kilograms, 10 kilograms for different models and different design.
- Aerosol agent storage pressure: normal.
- Aerosol device model number: AW-QRR3GW/S, AW-QRR5GW/S, AW-QRR7.5GW/S, AW-QRR8GW/S, AW-QRR10GW/S, for details please refer to our “Installation Manual”.
- Aerosol design concentration: 130 gram to 150 gram per cubic meter, for details pleas inquiry to discuss.
- Dimension size of the product: normally diameter in 300 millimeters and length in 700 millimeters, could be design as per specialty.
- Start-up mode: Electrical or electronics by power supply of DC 3 to 24 Volt, and TAG thermal activation generator could be use together with this device.
- Working and operation temperature: from -40°C to +70°C.
- Extinguishing time: If aerosol mass is less than 1 kilograms, then the extinguishing time is less than 40 seconds, and if aerosol mass weight is more than 1 kilograms, then the extinguishing time is less than 120 seconds.
- Down time: less than 30 seconds.
- Outside shell temperature during the period of discharging: less than 180°C at 5 millimeters distance from the outlet location.
- Shell temperature at the device: less than 100 degree Celsius.
- Resistance of direct current: one to eight ohms.
- Activation current and time: 1 Ann each 5 milliseconds.
- Minimum activation current and time: 250 Millie-amps each 5 milliseconds.
- Maximum safety current and time: 150 milliamps each 5 minutes.
- Life cycle of condensed solid aerosol compound: 7 to 10 years.
- Wire connection terminal: 5 cores, including: 2 cores for activation purpose, 2 cores for test report purpose, and one for anti-static.
- Connection mode between devices: series connection, Series circuit.
For know of “Main material description”, “Relative standard”, “External and Internal Structure”, “Attention for transport and storage”, “After-sales service” please refer to Floor Type Aerosol, or as per our “INSTALLATION MANUAL“.
Wall mounted aerosol model number:
- AW-QRR5GW/S with aerosol mass quality of 5 kilograms, protect of volume at 35 cubic meters each device.
- AW-QRR7.5GW/S with aerosol mass quality of 7.5 kilograms, protect of volume at 53 cubic meters each device.
- AW-QRR8GW/S with aerosol mass quality of 8.0 kilograms, protect of volume at 57 cubic meters each device.
Attention for operation:
- Please read the “Installation Manual” carefully before doing installation job.
- The installation and commissioning job must be done by a professional skilled personnel.
- After installation, the fire extinguishing system and its device shall not move with easy.
- When there is a fire, people must evacuate from the fire protection zone immediately, and before escape people should close the doors and windows quickly.
- The life span of this kind of aerosol device is about 7 to 10 years.
- After aerosol device is discharging, people should wear a pair of gloves to remove it and clean the device up, and do not touch the cylinder in case of get burned.
- It is forbidden to take apart the device, in case of any accident.
- The fire alarm system’ standby power is forbidden to discharging in continue 24 hours and the standby power should change in every 4 years.
- The inspector should disconnect the fire alarm control systems to inspect the system yearly and keep in record.
- Before installation, installer should make sure the device is with power off.
Attention for installation:
- Because this wall mounted fixed aerosol fire protection system device is need to install on the wall or on the top of ceiling, and each device will be several tens of kilograms in gross weight, so when install it take care and make sure to firmly fix the bracket and screws.
- Better to Install it at least 1/2 high of the room height.
- Make sure the left side discharging outlet and right side discharging outlet without any obstacles.
Why we recommend of wall mounted aerosol for market:
Wall mounted aerosol is mostly install in computer rooms, data processing rooms, telecommunication rooms and other buildings, and in china we have many cases to install it in underground Integrated Pipe Gallery, which is a national projects in china.
Also it is cover more spaces and space saving to install, some protection zone will need to require a device which is a space saving device.
And aerosol extinguishing device is with very high extinguishing ability.
Safety Warning!
User should set warning sigh in the following obvious locations, the words on the warning sign suggest like follow:
- inside the protection zone: “WARNINGS! This is S type aerosol fire extinguishing device protection zone, if you hear there is a fire alarm at site, please escape immediately”.
- At location of the manual call point: “WARNING, When press down the manual call point button, please make sure there is no people at site”.
- Outside the protection zone: ” This protection zone is protected by aerosol fire extinguishing systems”.
Device Maintenance
to ensure of the reliability of hot aerosol fire extinguishing device, we should establish a complete regulations for equipment inspection and maintenance, and make operation norm; the qualified inspector should inspect it and make a record regularly.
During the maintenance period, the inspector must do inspection job in accordance with relevant standards and specifications.
1. Daily Maintenance (When device is being in use)
a. make sure the protection zone and fire alarm system control rooms are clean, dry and well ventilated.
b. make sure the surface of aerosol device and fire alarm control panel is without dust.
c. check the nameplate of the aerosol device, warning sign are intact, and check outlet of aerosol device is not blocked.
d. check whether the fire alarm system is with fault or not, or check whether it have activation problem or not; if find out any of above problem, then please check and resolve it in time.
2. Yearly Maintenance
- Protection area opening situations,aim of the protection area, protection types, quantities and distribution of combustibles, these factors should in accordance with fire protection standards and specifications.
- Exam all aspects of the aerosol extinguishing devices, for example, to inspect whether all the components and parts are firmly fixed or not, and please clean up the device to make sure it will not have much dust.
- After the aerosol units put in use, its expiration date is about 7 to 10 years, after the expiration date, please try to contact the supplier for replacement.
Aerosol fire protection system is have common features, normally described as follow:
- The third aerosol technology, and refill with strontium nitrate and potassium nitrate of aerosol chemical powder, strontium nitrate take proportion of about 50%, and potassium nitrate take about 10% to 20% proportion, china aerosol based compound is with advance technology and innovative.
- it is non-toxic, non corrosive, non conductive, not have any residue after suppression.
- It is Eco-friendly with zero value in Ozone-layer Depletion, Zero value in Global Warming Potential, Low value in Atmospheric Life Time.
- Space saving and compact, and simple construction, easy to install, easy to do system design, debugging and installation.
- Low in system maintenance after sale, not require years inspection.
Also wall mounted type of aerosol device have its special characteristics, there are listed as follow:
- Round cylinder shape like a indoor air conditioner.
- Could be install on the top ceiling of the room or on the wall above the protection objective, it is space saving for the project.
- IP 67 in water proof and dust proof performance.
Remark: hereby IP is IP code, which means what is the grade of dust protection and water protection.
Wall mounted style of aerosol suppression system is also have widely applied in many industries and protected object across post and telecommunication industry, mining industry, power industry, banking industry and so on, including:
- Computer room.
- Server room.
- Data processing room.
- Power Generator room.
- Power distribution room.
- Cable tray.
- Underground pipe gallery.
- Substation.
- UPS room.
- EPS room.
- Battery room.
- Storage room.
- Expensive medical room.
- Museum.
- Library.
- Archives.
- Vehicles engine room compartment.
- Wind Power.
- Health care room.
- Some other machinery facilities and equipment.
Aerosol fire extinguishing device and its system is apply in the following class Rating:
- Class A fires: common fuels, such as wood or trash.
- Class B fires: Flammable or combustible liquids, such as solvents and gasoline.
- Class C fires: Burning gases, such as natural gas.
- Class E fires: Fires involving potentinally energized electrical equipment.
- Class F fire: Vegetable or animal cooking oils and fats, such as kitchens.
And aerosol system is not suitable for the following sites:
- Chemicals that can oxidize quickly without air, like Nitrocellulose, gunpowder; or Chemicals that can break down by themselves, like hydrazine and some metal peroxides.
- Oxidized metal, like potassium and sodium etc; and metal oxide, like potassium hydride, sodium hydride etc; and Spontaneous combustion, like Phosphorus.
- Deep fire of flammable solid.